Page top

K3HB-X

Process Indicator

K3HB-X

A Process Indicator Ideal for Discriminating and Displaying Measurements for Voltage/Current Signals

Ratings

Power supply voltage 100 to 240 VAC (50/60 Hz), 24 VAC/VDC, DeviceNet power supply: 24 VDC
Allowable power supply voltage
range
85% to 110% of the rated power supply voltage, DeviceNet power supply: 11 to 25
VDC
Power consumption *1 100 to 240 V: 18 VA max. (max. load)
24 VAC/DC: 11 VA/7 W max. (max. load)
Current consumption DeviceNet power supply: 50 mA max. (24 VDC)
Input DC voltage, DC current, AC voltage, AC current
A/D conversion method Delta-Sigma method
External power supply 12 VDC ±10%, 80 mA (models with external power supply only)
Event
inputs
*2
Timing input NPN open collector or no-voltage contact signal
ON residual voltage: 3 V max.
ON current at 0 Ω: 17 mA max.
Max. applied voltage: 30 VDC max.
OFF leakage current: 1.5 mA max.
Startup compensation
timer input
NPN open collector or no-voltage contact signal
ON residual voltage: 2 V max.
ON current at 0 Ω: 4 mA max.
Max. applied voltage: 30 VDC max.
OFF leakage current: 0.1 mA max.
Hold input
Reset input
Forced-zero input
Bank input
Output
ratings
(depends
on the
model)
Relay output 250 VAC, 30 VDC, 5 A (resistive load)
Mechanical life expectancy: 5,000,000 operations, Electrical life expectancy:
100,000 operations
Transistor output Maximum load voltage: 24 VDC, Maximum load current: 50 mA, Leakage current:
100 μA max.
Linear output Linear output 0 to 20 mA DC, 4 to 20 mA DC:
Load: 500 Ω max, Resolution: Approx. 10,000, Output error: ±0.5% FS
Linear output 0 to 5 VDC, 1 to 5 VDC, 0 to 10 VDC:
Load: 5 kΩ max, Resolution: Approx. 10,000, Output error: ±0.5% FS
(1 V or less: ±0.15 V; no output for 0 V or less)
Display method Negative LCD (backlit LED) display
7-segment digital display (Character height: PV: 14.2 mm (green/red); SV: 4.9 mm
(green)
Main functions Scaling function, measurement operation selection, averaging, previous average
value comparison, forced-zero, zero-limit, output hysteresis, output OFF delay,
output test, teaching, display value selection, display color selection, key
protection, bank selection, display refresh period, maximum/minimum hold, reset
Ambient operating temperature -10 to 55 °C (with no icing or condensation)
Ambient operating humidity 25% to 85%
Storage temperature -25 to 65 °C (with no icing or condensation)
Altitude 2,000 m max.
Accessories Watertight packing, 2 fixtures, terminal cover, unit stickers, instruction manual.
DeviceNet models also include a DeviceNet connector (Hirose HR31-5.08P-5SC
(01)) and crimp terminals (Hirose HR31-SC-121) *3

*1. DC power supply models require a control power supply capacity of approximately 1 A per Unit when power is turned
       ON. Particular attention is required when using two or more DC power supply models. The OMRON S8VS-series DC
       Power Supply Unit is recommended.
*2. PNP input types are also available.
*3. For K3HB-series DeviceNet models, use only the DeviceNet Connector included with the product. The crimp terminals
       provided are for Thin Cables.

Characteristics

Display range -19,999 to 99,999
Sampling period 20 ms (50 times/second)
Comparative output
response time
DC input: 100 ms max.; AC input: 300 ms max.
(The time until the comparative output is output when there is a forced sudden change in
the input signal from 15% to 95% or 95% to 15%.)
Linear output response
time
DC input: 150 ms max.; AC input: 420 ms max.
(The time until the final analog output value is reached when there is a forced sudden
change in the output signal from 15% to 95% or 95% to 15%.)
Insulation resistance 20 MΩ min. (at 500 VDC)
Dielectric strength 2,300 VAC for 1 min between external terminals and case
Noise immunity 100 to 240 VAC models: ±1,500 V at power supply terminals in normal or common mode
(waveform with 1-ns rising edge and pulse width of 1 μs/100 ns)
24 VAC/VDC models: ±1,500 V at power supply terminals in normal or common mode
(waveform with 1-ns rising edge and pulse width of 1 μs/100 ns)
Vibration resistance Frequency: 10 to 55 Hz; Acceleration: 50 m/s2, 10 sweeps of 5 min each in X, Y, and Z
directions
Shock resistance 150 m/s2 (100 m/s2 for relay outputs) 3 times each in 3 axes, 6 directions
Weight Approx. 300 g (Base Unit only)
Degree of
protection
Front panel Conforms to NEMA 4X for indoor use (equivalent to IP66)
Rear case IP20
Terminals IP00 + finger protection (VDE0106/100)
Memory protection EEPROM (non-volatile memory)
Number of rewrites: 100,000
Applicable standards UL61010-1, CSA C22.2 No.61010-1-04
EN61010-1 (IEC61010-1): Pollution degree 2/Overvoltage category II
EN61326-1
EMC EMI: EN61326-1 Industrial electromagnetic environment
Electromagnetic radiation interference: CISPR 11 Group 1, Class A
Terminal interference voltage: CISPR 11 Group 1, Class A
EMS: EN61326-1 Industrial electromagnetic environment
Electrostatic Discharge Immunity: EN61000-4-2: 4 kV (contact), 8 kV (in air)
Radiated Electromagnetic Field Immunity: EN61000-4-3: 10 V/m 1 kHz sine wave amplitude
modulation (80 MHz to 1 GHz, 1.4 to 2 GHz)
Electrical Fast Transient/Burst Immunity: EN61000-4-4: 2 kV (power line), 1 kV (I/O signal
line)
Surge Immunity: EN61000-4-5: 1 kV with line (power line), 2 kV with ground (power line)
Conducted Disturbance Immunity: EN61000-4-6: 3 V (0.15 to 80 MHz)
Power Frequency Magnetic Immunity: EN61000-4-8: 30 A/m (50 Hz) continuous time
Voltage Dips and Interruptions Immunity: EN61000-4-11: 0.5 cycle, 0°/180°, 100% (rated
voltage)

Input Range (Measurement Range and Accuracy) CAT II

Input
type
Range Set
value
Measurement
range
Maximum
measurement
range
Input
impedance
Accuracy Allowable
instantaneous
overload (30 s)
K3HB-XVD
DC voltage
A
1535_sp_3_1
±199.99 V -199.99 to 219.99 V 10 MΩ min. ±0.1%rdg
± 1 digit max.
±400 V
B
1535_sp_3_2
±19.999 V -19.999 to 21.999 V 1 MΩ min. ±200 V
C
1535_sp_3_3
±1.9999 V -1.9999 to 2.1999 V
D
1535_sp_3_4
1.0000 to 5.0000 V 0.5000 to 5.5000 V
K3HB-XAD
DC current
A
1535_sp_3_5
±199.99 mA 199.99 to 219.99 mA 1 Ω max. ±0.1%rdg
± 1 digit max.
±400 mA
B
1535_sp_3_6
±19.999 mA 19.999 to 21.999 mA 10 Ω max. ±200 mA
C
1535_sp_3_7
±1.9999 mA 1.9999 to 2.1999 mA 33 Ω max.
D
1535_sp_3_8
4.000 to 20.000 mA 2.000 to 22.000 mA 10 Ω max.
K3HB-XVA
AC voltage
*4
A
1535_sp_3_9
0.0 to 400.0 V 0.0 to 440.0 V 1 MΩ min. ±0.3%rdg
± 5 digits max.
700 V
B
1535_sp_3_10
0.00 to 199.99 V 0.00 to 219.99 V
C
1535_sp_3_11
0.000 to 19.999 V 0.000 to 21.999 V ±0.5%rdg
± 10 digits
max.
400 V
D
1535_sp_3_12
0.0000 to 1.9999 V 0.0000 to 1.9999 V
K3HB-XAA
AC current
A
1535_sp_3_13
0.000 to 10.000 A 0.000 to 11.000 A (0.5 VA CT)
*3
±0.5%rdg
± 20 digits
max.
20 A
B
1535_sp_3_14
0.0000 to 1.9999 A 0.0000 to 2.1999 A (0.5 VA CT)
*3
C
1535_sp_3_15
0.00 to 199.99 mA 0.00 to 219.99m A 1 Ω max. ±0.5%rdg
± 10 digits
max.
2 A
D
1535_sp_3_16
0.000 to 19.999 mA 0.000 to 21.999m A 10 Ω max.

*1. The accuracy is for an input frequency range of 40 Hz to 1 kHz (except for AD current input A and B ranges of 50 to
       60 Hz) and an ambient temperature of 23 ±5°C. The error, however, increases below 10% of the maximum input
       value.
       DC voltage input (all ranges): 10% or less of max. input = ±0.15% FS
       DC current input (all ranges): 10% or less of max. input = ±0.1% FS
       AC voltage input (A: 0.0 to 400.0 V): 10% or less of max. input = ±0.15% FS
       AC voltage input (B: 0.00 to 199.99 V): 10% or less of max. input = ±0.2% FS
       AC voltage input (C: 0.000 to 19.999 V; D: 0.0000 to 1.9999 V): 10% or less of max. input = ±1.0% FS
       AC current input (A: 0.000 to 10.000 A): 10% or less of max. input = ±0.25% FS
       AC current input (B: 0.0000 to 1.9999 A): 10% or less of max. input = ±0.5% FS
       AC current input (C: 0.00 to 199.99 mA; D: 0.000 to 19.999 A): 10% or less of max. input = ±0.15% FS
       When DC voltage input models are used with a ±1.9999 V range, make sure that the connections between input
       terminals are not open.
       If the input terminals are open, the display will show large variations. Connect resistance of approximately 1 MΩ
       between the input terminals if they are open.
*2. The letters "rdg" mean "reading" and refer to the input error.
*3. The value (0.5 VA CT) is the VA consumption of the internal CT (current transformer).

K3HB-X Specifications 5

*4. The K3HB-XVA[][] complies with UL standards when the applied input voltage is within the range 0 to 150 VAC.
       If the input voltage is higher than 150 VAC, install an external transformer or take other measures to drop the voltage
       to 150 VAC or lower.