| Type | CP1L-M60 (60 points)
 | CP1L-M40 (40 points)
 | CP1L-M30 (30 points)
 | CP1L-L20 (20 points)
 | CP1L-L14 (14 points)
 | CP1L-L10 (10 points)
 | 
								
									| Models | CP1L- M60[][]-[]
 | CP1L- M40[][]-[]
 | CP1L- M30[][]-[]
 | CP1L- L20[][]-[]
 | CP1L- L14[][]-[]
 | CP1L- L10[][]-[]
 | 
								
									| Control method | Stored program method | 
								
									| I/O control method | Cyclic scan with immediate refreshing | 
								
									| Program language | Ladder diagram | 
								
									| Function blocks | Maximum number of function block definitions: 128 Maximum number of instances: 256 Languages usable in function block definitions: Ladder diagrams, structured text (ST)
 | 
								
									| Instruction length | 1 to 7 steps per instruction | 
								
									| Instructions | Approx. 500 (function codes: 3 digits) | 
								
									| Instruction execution time
 | Basic instructions: 0.55 μs min. Special instructions: 4.1 μs min. | 
								
									| Common processing time
 | 0.4 ms | 
								
									| Program capacity | 10K steps | 5K steps | 
								
									| Number of tasks | 288 (32 cyclic tasks and 256 interrupt tasks) | 
								
									|  | Scheduled interrupt
 tasks
 | 1 (interrupt task No. 2, fixed) | 
								
									| Input interrupt
 tasks
 | 6 (interrupt task No. 140 to 145, fixed) | 4 (interrupt task No. 140
 to 143, fixed)
 | 2 (interrupt task No. 140
 to 141, fixed)
 | 
								
									| (Interrupt tasks can also be specified and executed for high-speed counter interrupts and executed.)
 | 
								
									| Maximum subroutine number
 | 256 | 
								
									| Maximum jump number | 256 | 
								
									| I/O areas
 | Input Area | 1,600 bits (100 words) CIO 0 to CIO 99 | 
								
									|  | Built-in Input Area
 | 36 bits: CIO 0.00 to CIO
 0.11 and CIO
 1.00 to CIO
 1.11 and CIO
 2.00 to CIO
 2.11
 | 24 bits: CIO 0.00 to CIO
 0.11 and CIO
 1.00 to CIO
 1.11
 | 18 bits: CIO 0.00 to CIO
 0.11 and CIO
 1.00 to CIO
 1.05
 | 12 bits: CIO 0.00 to CIO
 0.11
 | 8 bits: CIO 0.00 to CIO
 0.07
 | 6 bits: CIO 0.00 to CIO
 0.05
 | 
								
									| Output Area | 1,600 bits (100 words) CIO 100 to CIO 199 | 
								
									|  | Built-in Output
 Area
 | 24 bits: CIO 100.00 to CIO
 100.07 and
 CIO 101.00 to
 CIO 101.07
 and CIO
 102.00 to CIO
 102.07
 | 16 bits: CIO 100.00 to CIO
 100.07 and
 CIO 101.00 to
 CIO 101.07
 | 12 bits: CIO 100.00 to CIO
 100.07 and
 CIO 101.00 to
 CIO 100.03
 | 8 bits: CIO 100.00 to
 CIO 100.07
 | 6 bits: CIO 100.00 to
 CIO 100.05
 | 4 bits: CIO 100.00 to
 CIO 100.03
 | 
								
									| 1:1 Link Area
 | 1,024 bits (64 words): CIO 3000.00 to CIO 3063.15 (CIO 3000 to CIO 3063) | 
								
									| Serial PLC Link Area
 | 1,440 bits (90 words): CIO 3100.00 to CIO 3189.15 (CIO 3100 to CIO 3189) | 
								
									| Work bits | 8,192 bits (512 words): W000.00 to W511.15 (W0 to W511) CIO Area: 37,504 bits (2,344 words): CIO 3800.00 to CIO 6143.15 (CIO 3800 to CIO 6143)
 | 
								
									| TR Area | 16 bits: TR0 to TR15 | 
								
									| Holding Area | 8,192 bits (512 words): H0.00 to H511.15 (H0 to H511) | 
								
									| AR Area | Read-only (Write-prohibited): 7168 bits (448 words): A0.00 to A447.15 (A0 to A447) Read/Write: 8192 bits (512 words): A448.00 to A959.15 (A448 to A959)
 | 
								
									| Timers | 4,096 timer numbers: T0 to T4095 | 
								
									| Counters | 4,096 counter numbers: C0 to C4095 | 
								
									| DM Area | 32 Kwords: D0 to D32767 | 10 Kwords: D0 to D9999, D32000 to D32767
 | 
								
									| Data Register Area | 16 registers (16 bits): DR0 to DR15 | 
								
									| Index Register Area | 16 registers (32 bits): IR0 to IR15 | 
								
									| Task Flag Area | 32 flags (32 bits): TK0000 to TK0031 | 
								
									| Trace Memory | 4,000 words (500 samples for the trace data maximum of 31 bits and 6 words.) | 
								
									| Memory Cassette | A special Memory Cassette (CP1W-ME05M) can be mounted. Note: Can be used for program backups and auto-booting.
 | 
								
									| Clock function | Supported. Accuracy (monthly deviation): -4.5 min to -0.5 min (ambient temperature: 55°C), -2.0 min to +2.0 min (ambient temperature: 25°C),
 -2.5 min to +1.5 min (ambient temperature: 0°C)
 | 
								
									| Communications functions
 | One built-in peripheral port (USB 1.1): For connecting Support Software only. | 
								
									| A maximum of two Serial Communications Option Boards can be mounted.
 | A maximum of one Serial Communications Option
 Board can be mounted.
 | Not supported.
 | 
								
									| A maximum of two Ethernet Option Board can be mounted.
 When using CP1W-CIF41 Ver.1.0, one
 Ethernet Option Board can be mounted.
 | A maximum of one Ethernet Option Board
 can be mounted.
 | Not supported.
 | 
								
									| Memory backup | Flash memory: User programs, parameters (such as the PLC Setup), comment data, and the entire DM Area can be saved to flash memory as initial values.
 Battery backup: The Holding Area, DM Area, and counter values (flags, PV) are backed up by a
 battery.
 | 
								
									| Battery service life | Service life expectancy is 5 years at 25°C, less at higher temperatures. (From 0.75 to 5 years depending on model, power supply rate, and ambient temperature.)
 | 
								
									| Built-in input terminals
 | 60 (36 inputs,
 24 outputs)
 | 40 (24 inputs,
 16 outputs)
 | 30 (18 inputs,
 12 outputs)
 | 20 (12 inputs,
 8 outputs)
 | 14 (8 inputs,
 6 outputs)
 | 10 (6 inputs,
 4 outputs)
 | 
								
									| Number of connectable
 Expansion Units and
 Expansion I/O Units
 | CP-series Expansion Unit and Expansion I/O Units: 3 max.
 | CP-series Expansion Units and Expansion I/O Units: 1 max.
 | Not supported.
 | 
								
									| Max. number of I/O points
 | 180 (60 built in + 40 per
 Expansion
 (I/O) Unit
 × 3 Units)
 | 160 (40 built in + 40 per
 Expansion
 (I/O) Unit
 × 3 Units)
 | 150 (30 built in + 40 per
 Expansion
 (I/O) Unit
 × 3 Units)
 | 60 (20 built in + 40 per
 Expansion
 (I/O) Unit
 × 1 Unit)
 | 54 (14 built in + 40 per
 Expansion
 (I/O) Unit
 × 1 Unit)
 | 10 (10 built in)
 | 
								
									| Interrupt inputs | 6 inputs (Response time: 0.3 ms) | 4 inputs (Response
 time: 0.3 ms)
 | 2 inputs (Response
 time: 0.3 ms)
 | 
								
									| Interrupt inputs counter mode
 | 6 inputs (Response frequency: 5 kHz max. for all interrupt inputs), 16 bits
 Up or down counters
 | 4 inputs (Response
 frequency:
 5 kHz max.
 for all
 interrupt
 inputs), 16
 bits Up or
 down
 counters
 | 2 inputs (Response
 frequency:
 5 kHz max.
 for all
 interrupt
 inputs), 16
 bits Up or
 down
 counters
 | 
								
									| Quick-response inputs | 6 points (Min. input pulse width: 50 μs max.) | 4 points (Min. input pulse
 width: 50 μs
 max.)
 | 2 points (Min. input pulse
 width: 50 μs
 max.)
 | 
								
									| Scheduled interrupts | 1 | 
								
									| High-speed counters | 4 inputs/2 axes (24 VDC): Differential phases (4x), 50 kHz
 Single-phase (pulse plus direction, up/down, increment), 100 kHz
 Value range: 32 bits, Linear mode or ring mode
 Interrupts: Target value comparison or range comparison
 | 
								
									| Pulse outputs
 (models
 with
 transistor
 outputs
 only)
 | Pulse outputs
 | Trapezoidal or S-curve acceleration and deceleration (Duty ratio: 50% fixed) 2 outputs, 1 Hz to 100 kHz (CCW/CW or pulse plus direction)
 | 
								
									| PWM outputs
 | Duty ratio: 0.0% to 100.0% (specified in increments of 0.1% or 1%) 2 outputs, 0.1 to 6553.5 Hz or 1 to 32,800 Hz (Accuracy: +1%/0% at 0.1 Hz to 10,000 Hz and
 +5%/0% at 10,000 Hz to 32,800 Hz)
 | 
								
									| Analog control | 1 (Setting range: 0 to 255) | 
								
									| Analog input | 1 input (Resolution: 1/256, Input range: 0 to 10 V). Not isolated. |